A. 总则..........................................................................................1
-
B. 建筑制热/ 制冷荷载的计算原则.................................................2
-
C. 采暖
通风空调系统
要求.............................................................3
-
D. 中央制冷站(机房).................................................................5
-
E. 中央制热站(机房).................................................................8
-
F. 管道系统.................................................................................10
-
G. 全空气空调系统......................................................................13
-
H. 公共区和后勤的全空气空调机组.............................................16
-
I. 客房 / 客房层通道补风用空调系统...........................................18
-
J. 风管.........................................................................................20
-
K. 防排烟系统.............................................................................23
-
L. 燃油系统................................................................................25
-
M. 系统的测试和平衡调节............................................................26
-
N. 室内温度自动控制 (ATC) 和 楼宇管理系统 (BMS)...................26
-
O. 表 15A-1 – 室内环境要求.......................................................29
附件详情
稿件为某知名酒店集团机电设计标准--暖通空调系统设计;包括采暖、空调、通风、防排烟系统设计标准,以及冷热源机房设计标准,楼宇管理系统等等。
中央制冷站(机房)设计要点:
中央制冷系统具有较高能源及运行效率。典型的系统构成包括有:高效能的水冷主机;一级/二级冷冻水泵系统(含旁通及多个二级回路);定流量的冷却水泵系统和冷却塔。其他辅助设备包括膨胀水箱、汽水分离器、化学水处理系统。
• 冬季条件: 在天气寒冷区域采用水侧节能系统(*利用水/水热交换器)。
• 服务范围: 供应冷冻水至公共区和后勤区的中央空气处理机和客房区的风机盘管。
• 位置选择:主机房位置的定位要考虑尽量减少管道和线管的长度,可能时设在地面层以便于维修作业,但须在空调区之外。要考虑到地下水位高度及防涝设计。
• 主机水管临时接口:考虑到主机有故障时可能需要接上临时机组,在冷冻水和冷却水主管系统上配备两套带阀门的法兰接口。
• 地区性要求: 须征询万豪A&C工程部确认的要求 :
+ 基于地理位置,当地技术服务人员质素以及设备配件货源的考虑,增加制冷主机, 水泵及冷却塔台数。
……